Pixsys ATR244 Controller User Manual

ATR244 Universal Controller

The ATR244 is an industrial digital controller/regulator designed for indoor process control applications. Follow the safety guidelines before connecting, installing, or configuring the unit.

Technical Specifications (Extracted)

Модель ATR244 (series with 5 versions)
Отображать 4 digits, 0.52″ OR 5 digits, 0.30″
Рабочая температура 0–45 °С
Влажность 35–95 uR% (as stated)
Защита IP65 front panel (with gasket); IP20 box and terminals (UL not evaluated)
Материал корпуса Box: PC UL94V2 self-extinguishing; Front panel: PC UL94V2 self-extinguishing
Масса Около 185 г
Охлаждение “Cooling” listed under hardware features (details not included in extracted text)
AI1/AI2 (Analog inputs) Configurable via software; accepts thermocouples (types K, S, R, J, T, E, N, B) and thermoresistances (PT100, PT500, PT1000, Ni100, PTC 1K, NTC 10K (3435K)), and V/mA inputs (0–1 V, 0–5 V, 0–10 V, 0–20/4–20 mA, 0–60 mV). Cold junction compensation: -25..85 °C.
AI input accuracy (thermocouples/thermoresistance/V-mA) Thermocouples/RTD: ±0.2% 1 digit (as stated for F.s.); cold junction accuracy 0.1 °C/°C; V/mA ranges include stated resolution/points (details below).
Аналоговый входной импеданс 0–10 V: Ri>110 kΩ; 0–20 mA: Ri≈1 MΩ (as extracted)
Аналоговые выходы Configurable as command/alarm or retransmission; 0–10 V with 40000 points ±0.2% (as stated); 4–20 mA with 40000 points ±0.2% (as stated)
Релейные выходы Configurable as command and alarm outputs; contacts: 2 A – 250 VAC for resistive loads
SSR outputs Configurable as command and alarm outputs; 12/24 V, 25 mA
Supply ranges ATR244-12xxx and -13ABC: 24..230 VAC/VDC (15%, 50/60 Hz) 6 Watt/VA
ATR244-23A-T: 24 VAC/VDC (15%, 50/60 Hz) 6 Watt/VA
ATR244-23BC-T: 115..230 VAC (15%, 50/60 Hz) 6 Watt/VA
Relay/power supply terminal screw tightening torque 0.51 Нм
Other terminals tightening torque 0.19 Нм
Loading PDF…
Download PDF

Troubleshooting Guidance (Extracted)

  • Unexpected loss of control/alarm outputs: If a malfunction in the Digital Controller occurs, control operations may be impossible and/or alarm outputs may not work. Take appropriate safety measures, such as installing a monitoring device on a separate line.
  • Probe error alarm: A “Probe error” alarm is active in case of sensor breakage.
  • Relay life / overheating-related issues: The product notes that if output relays are used past their life expectancy, contact fusing or burning may occasionally occur—ensure output relays are used within their rated load and electrical life expectancy.
  • Incorrect relay terminal tightening: Loose screws may occasionally result in fire. Tighten relay and power supply screw terminals to the specified torque (0.51 Nm) and other terminals to 0.19 Nm.

Часто задаваемые вопросы

What should I do before making hardware settings or electrical wiring changes?
Disconnect the power supply before proceeding to hardware settings or electrical wirings to avoid the risk of electric shock and fire/malfunction.
What does “Probe error” indicate?
“Probe error” is an alarm active in case of sensor breakage.
What is the required tightening torque for relay and power supply screw terminals?
Tighten screws to a tightening torque of 0.51 Nm for screw terminals of relays and of the power supply.

Документы/Ресурсы

миниатюра PDFATR244 Controller
User Manual · ATR244, ATR244 Controller, Controller

Задать вопрос

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Задать вопрос

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.