Введение
This manual provides instructions for the installation, operation, and maintenance of the Intermatic T174 DPST 24 Hour Time Switch. This electromechanical timer is designed for controlling electrical loads over a 24-hour period.
Image: Intermatic T174 DPST 24 Hour Time Switch. This image shows the front view of the timer with its gray metal enclosure and the dial for setting time.
Информация по безопасности
WARNING: Risk of electric shock. Installation and servicing must be performed by qualified personnel only. Disconnect power at the circuit breaker or fuse box before installing or servicing the timer.
- Всегда соблюдайте местные электротехнические нормы и правила.
- Убедитесь, что блок питания соответствует громкости таймера.tage rating (208-277V AC).
- Do not exceed the maximum current and horsepower ratings of the timer.
- This device is intended for indoor use in a Type 1 enclosure.
Содержимое упаковки
The Intermatic T174 Time Switch package typically includes:
- One (1) Intermatic T174 Time Switch Unit
- Руководство по эксплуатации
- Two (2) Trippers for setting ON/OFF times
Настройка и установка
The Intermatic T174 is designed for fixed installation. Proper wiring is crucial for safe and correct operation.
Монтаж
- Choose a suitable indoor location for mounting the timer, ensuring it is protected from moisture and extreme temperatures.
- Securely mount the timer's enclosure to a wall or suitable surface using appropriate fasteners.
Wiring (DPST Configuration)
The T174 features a Double Pole, Single Throw (DPST) contact form, meaning it controls two independent circuits or a single 2-pole circuit simultaneously.
- DISCONNECT ALL POWER to the circuit at the main service panel before proceeding.
- Open the timer's enclosure.
- Connect the incoming power lines (L1 and L2 for 208-277V AC) to the designated "LINE" terminals on the timer.
- Connect the load wires (to the device being controlled) to the designated "LOAD" terminals. Ensure correct polarity if applicable.
- Убедитесь, что все соединения проводов надежны и герметичны.
- Close the timer's enclosure securely.
- Восстановите питание цепи.
Если вы не уверены в правильности выполнения каких-либо процедур электромонтажа, проконсультируйтесь с квалифицированным электриком.
Инструкция по эксплуатации
The T174 uses a mechanical dial and trippers to set the ON/OFF schedule.
Установка текущего времени
- Rotate the timer dial clockwise until the current time aligns with the "TIME SET" arrow or indicator on the timer mechanism.
- Ensure AM/PM is correctly observed if the dial has such markings.
Setting ON/OFF Times
The timer comes with two trippers: one "ON" tripper and one "OFF" tripper. Additional trippers can be purchased separately (Extra Trippers 11Z965).
- Locate the "ON" tripper (typically silver or light-colored) and the "OFF" tripper (typically black or dark-colored).
- Snap the "ON" tripper onto the dial at the desired time you want the connected device to turn ON.
- Snap the "OFF" tripper onto the dial at the desired time you want the connected device to turn OFF.
- You can set up to 12 ON/OFF cycles per 24-hour period using additional trippers. The minimum time setting is 1 hour.
Ручное управление
The T174 typically includes a manual override switch or lever. This allows you to temporarily turn the connected device ON or OFF without affecting the programmed schedule. Refer to the specific markings on your timer for the manual override function.
Day Skipper Function
The timer features a Day Skipper function, allowing you to prevent operation on specific days of the week. Consult the detailed instruction guide included with your unit for specific setup of this feature.
Обслуживание
The Intermatic T174 Time Switch is designed for reliable, long-term operation with minimal maintenance.
- Periodically inspect the timer for any signs of damage or loose connections.
- Keep the enclosure clean and free from dust and debris.
- Do not attempt to lubricate internal components.
Поиск неисправностей
| Проблема | Возможная причина | Решение |
|---|---|---|
| Таймер не работает. | Таймер не получает питания. | Check circuit breaker or fuse. Ensure wiring connections are secure. |
| Connected device does not turn ON/OFF at programmed times. | Incorrect tripper placement or current time setting. | Verify tripper positions and ensure the current time is accurately set on the dial. Check manual override switch position. |
| Timer motor is noisy. | Normal operation for some mechanical timers. | If noise is excessive or new, contact support. |
| Timer operates but device does not. | Faulty wiring to the load or issue with the connected device. | Verify load wiring. Test the connected device directly to ensure it is functional. |
Технические характеристики
| Особенность | Деталь |
|---|---|
| Номер модели | Т174 |
| Тип | Электромеханический таймер |
| Операция | 24-часовой |
| Количество полюсов | 2 |
| Контактная форма | DPST-NO (Double Pole, Single Throw - Normally Open) |
| Томtage | 208-277V AC |
| Ampярость | 40 А |
| Contact HP @ 120V | 2 л.с. |
| Contact HP @ 240V | 5 л.с. |
| Day Skipper | Да |
| Тип корпуса | Steel, Type 1 Indoor Enclosure |
| Заканчивать | Серая эмаль |
| Minimum Time Setting | 1 час |
| Настройка максимального времени | 23 часа |
| Maximum ON/OFF Cycles | 12 |
| Размеры (В x Ш x Г) | 7 13/16 in x 5 in x 3 in (Approximate) |
| Вес товара | 2.75 - 2.8 фунта |
| Included Trippers | 2 |
| СКП | 078275174214 |
| Производитель | Интерматик Инкорпорейтед |
Гарантия и поддержка
The Intermatic T174 Time Switch comes with a manufacturer's warranty. For specific warranty details, please refer to the documentation included with your product or visit the official Intermatic webсайт.
For technical support, troubleshooting assistance, or to inquire about replacement parts, please contact Intermatic customer service. You can often find support information and additional resources on the Intermatic Store on Amazon или их официальное корпоративное webсайт.